SK07-TTHC-4B  (ohne phys. Sensoren)
ARCUS SK07-TTHC-4B

SK07-TTHC-4B (ohne phys. Sensoren)

Product code: 30540780
The KNX-Sensor SK07-TTHC-4B is used for measuring and controlling indoor air parameters
Price (Excluding GST)
$P.O.A

Description

  • Air temperature (external connection, PT1000)
  • Air temperature and humidity (external connection, SHT71)
  • Calculated values absolute humidity, dew point temperature and energy content (enthalpy)
  • Primary temperature input also weighted with additional mixing temperature
  • Control functions for heating and cooling applications (can be combined)
  • Setpoint temperatures for Comfort, Standby, Economy and Protection, selectable via KNX HVAC objects
  • Setpoint change via objects
  • Storage of minimum and maximum temperature
  • Heat and frost alarm
  • Limits for temperature, humidity
  • Fan control via humidity limits and external inputs
  • Detecting of dew point temperature with alarm / regulation at risk of condensation
  • Adaptation for setpoint and limits temperatures
  • Controller output 0..100% or programmable PWM for thermal actuators
  • Valve rinse function
  • Second temperature controller as auxiliary controller
    Four binary inputs / outputs (floating)
  • Light control as switch / button with short, long, double and both function
  • Dimmer
  • Blind and shutter control
  • Programmable Encoder
  • Temperature adjustment
  • The binary inputs can be configured as outputs (LED / Beeper)
    Four logic blocks for the logical link between internal and external signals
  • 10 associated logic inputs / outputs
  • Heat- and cooling-request as additionally available signals
  • Functions "AND, OR, NOT, XOR" for binary logic
  • Functions "+ - *" for 8-bit values
  • Function "=" for conditional forwarding of events
    Applications
  • Detection and control of room temperature and humidity
  • Decentralised control for steady KNX-valves or thermal actuators
  • Decentralised ventilation control depending on humidity and air quality
  • Detecting of component temperature and temperature control to prevent condensation and structural damage
  • Evaluation of external switches and push buttons for switching functions

Technical Details

Specification

Measurement: Temperature ( PT1000 ), Temperature / rel. Humidity ( SHT71 )

Calculated Values:: abs. Humidity, Dewpoint Temperature, Enthalpy

Control:ling: Integrated

Temperature Range: ( PT1000 ): -50 .. +400C

Accuracy:: ± 0,3C ( depending on the sensor used )

Resolution:: ± 0,01C

Temperature Range: ( SHT ): -20 .. +80C

Accuracy:: ± 0,3C

Resolution:: ± 0,01C

rel. Humidity Range ( SHT ): 0 .. 100% r.H

Resolution:: ± 3% r.H (20..80%) at +20C, else ± 5% r.H

Binary In- / Output: 4

Operating Voltage:: KNX Bus Voltage 21 .. 32VDC

Power Consumption:: approx. 240mW ( at 24VDC )

Environment Temperature KNX Module: Storage: -25 .. +85C, Operating: -25..+80C

Environment Humidity KNX Module: 0 .. 95% r.H Non Condensing

Bus Coupler:: Integrated

Auxiliary Supply:: Not Required

Startup with the ETS Version 4 or higher:: HLK305

Connection: KNX-2-Pole Clamps ( red / black )

Protection Class:: IP20

Housing KNX Module: Plastic

Dimensions KNX Module: ( 50 x 50 x 20 ) mm ( W x H X D ), 55mm diagonal ( for a standard flush-mounted box)

Properties

Properties

Technology KNX
Brand ARCUS
EAN 642000000000
Ivory Egg uses cookies to make your experience better and provide necessary site functionality. By using our website, you agree to set the cookies and accept the privacy policy