KNX Sensor Temperature Humidity Control VOC Concentration Rotary Controller + 2 Binary Inputs / Outputs - white
Description
- Air temperature ( sensor in the housing ) also weighted with external temperature
- Humidity ( sensor in the housing )
- VOC level ( volatile organic compound ) ( sensor in the housing )
- Calculated values absolute humidity, dew point temperature and energy
content ( enthalpy ) - Control functions for heating and cooling applications ( can be combined )
- Setpoint temperatures for Comfort, Standby, Economy and Protection,
selectable via KNX HVAC objects - Setpoint change via rotary controller and/or objects
- Storage of minimum- and maximum-temperature
- Heat- and frost-alarm
- Limits for temperature, humidity and VOC level
- Fan control by humidity, VOC limits and external inputs
- Detecting of dew point temperature and alarm / regulation at risk of
condensation - Adaptation for setpoint and maximum temperatures
- Controller output 0...100% or programmable PWM for thermal actuators
- Valve rinse function
- Second temperature controller as auxiliary controller
Rotary controller
Two binary inputs / outputs ( floating ) - Light control as switch / button with short, long, double and both function
- Dimmer
- Blind and shutter control
- Programmable Encoder
- Temperature adjustment
- The binary inputs can be configured as outputs ( LED / Beeper )
- Rotary controller to change the operational state ( comfort / standby ) and increase / decrease the setpoint temperature in
several steps
The current state of the temperature controller can be indicated by LEDs. - Heating or cooling
- Slow pulsing if controller is active
- Pulse depth represents deviation between actual- and setpoint-temperature
- Display for comfort / standby / night mode configurable
Four logic blocks for the logical link between internal and external signals. - 10 associated logic inputs / outputs
- Heat- and cooling-request as additionally available signals
- Functions "AND, OR, NOT, XOR" for binary logic
- Functions "+ - *" for 8-bit values
- Function "=" for conditional forwarding of events
Applications - Detection and control of room temperature and humidity
- Detection of VOC level
- Decentralized control for steady KNX-valves or thermal actuators
- Decentralized ventilation control depending on humidity and air quality
- Evaluation of external switches and push buttons for switching functions
Technical Details
Specification
Measurement: temperature rel. humidity VOC concentration
Calculated Values: abs. humidity dewpoint temperature enthalpie
Control: integrated
Temperature Range: -25 .. +80C
Resolution: 0.02C
Accuracy: ± 0.4C (5..60C), else ± 0.8C
Humidity Range: 10 .. 95% r.H
Resolution: 0.02% r.h
Accuracy: ± 3% r.H ( 20..80% ) at +20C, else ± 5% r.H
Measurement Range VOC 400 - 10000 ppm , CO2 equivalents
Rotary Controller Setpoint adjustment ( max. ± 5C )
Binary In / Output 2
Operating Voltage: KNX bus voltage 21 .. 32VDC
Power Consumption: approx. 240mW ( at 24VDC )
Environment Temperature KNX-Module: Operating: -25 .. +80C Storage: -25 .. +80C
Environment Humidity KNX-Module: 10 .. 95% r.H non condensing
Bus Coupler: integrated
Startup with the ETS Version 4 or higher: HLK305
Circuit Points:: KNX 2 pole clamps ( red / black )
Protection Class: IP20
Housing KNX-Module: plastic
Dimensions Housing KNX-Module: 55mm standard frame size
Properties
Properties
Technology | KNX |
Brand | ARCUS |
EAN | 642000000000 |