MAXinBOX  FC 0-10V VALVE. Fan coil controller for 2/4-pipe units with 0-10 VDC valve control signal
ZENNIO ZCL-FC010V

MAXinBOX FC 0-10V VALVE. Fan coil controller for 2/4-pipe units with 0-10 VDC valve control signal

Product code: ZCLFC010V
Controller for one 2-pipe or 4-pipe fan coil unit with 0-10V valves. Its 4 16A C-load outputs can be used to control the fan speed or as individual outputs. It has thermostat function and 4 analog-digital multifunction inputs that can be configured as binary inputs for sensors and potential-free push buttons, as temperature probe inputs or as motion sensor inputs. It includes a module with 10 logical functions and allows manual control of the outputs with status indication through LEDs.
Price (Excluding GST)
$P.O.A

Description

  • 2 x 0-10VDC individual outputs for valve control.
  • 4 individual outputs (suitable for capacitive loads, maximum 140µF) capable to control up to 4 fan speed.
  • 4 analog/digital inputs.
  • Manual output operation in 0-10VDC and individual outputs with push button and status indicator LED.
  • Logical functions included.
  • Output timing facilities.
  • Total data saving on power failure.
  • DIN rail unit assembly (EN 50022), with snap fit clamp.
  • Size 67 x 90 x 80 mm (40.5 DIN units).
  • KNX BCU integrated
  • Possibility to connect different phases in adjoining outputs.
  • CE directives compliant.

Technical Details

Specification

General System Specifications

  • KNX Power Supply: 29VDC
  • KNX Current Consumption: 11mA @ 29VDC
  • Operating temperature: 0 ¡C to 55 ¡C
  • Assembly: Independent control assembly device to be mounted inside of electrical panels with DIN rail (EN 50022).
  • KNX bus  failure response: Data saving
  • Response when restarting KNX bus: Data recovering and output status change according to programming when recovering.
  • Operation Indicator: Programming LED indicates programming mode (red) and test mode (green). Output status LED indicators show current output state.

Individual Output Specifications

  • Contact type: Potential free outputs through bistable relays with tungsten pre-contact.
  • Disconnection type: Micro-disconnection
  • Rated current by output: 16A (6)  250V AC (4000 VA), 16A (6) 30V DC (480W)
  • Maximum Power - Resistive load: 4000W
  • Maximum Power - Inductive load: 1500VA
  • Maximum inrush current: 800A/200_s, 165A/20ms
  • Outputs per common (channel): 1 individual output.
  • Different phase connection: Possibility to connect different phases in adjoining outputs
  • Connection type: Terminal block (screw)
  • Recommended cable section: 0.25 mm to 4 mm (26-10 AWG)
  • Cable type: Stranded or solid wire
  • Maximum response time: 50 ms
  • Expected life - Mechanical: 3 million operations (60cpm)
  • Expected life - Electrical: 100.000 cycles (6cpm/resistive load)

0-10V Output Specifications

  • Output voltage: From 0 to 10VDC
  • Output current: Maximum 10.5mA per output
  • Outputs per common: 1
  • Connection type: Terminal block (screw)
  • Recommended cable section: 0.15 mm to 20.5 mm 
  • Cable type Stranded or solid wire

Input Specifications 

  • Number of inputs per common: 4
  • Input voltage: +3.3V DC for the common
  • Input current: 1.0mA @ 3.3V DC (each input)
  • Input impedance: Approx. 3.3k ½
  • Switching type: Dry voltage contacts between input and common
  • Connection method: Cable screw terminal
  • Max. cable length: 30 m.
  • NTC probe length: 10.5 m. (max. 30m.)
  • NTC accuracy (@ 25 ¡C): 0.5 ¡C
  • Temperature measure precision: 0.1 ¡C
  • Cable cross-section: 0.15 mm to 20.5 mm (26-12 AWG)
  • Response time:  Max 10ms. 

Properties

Properties

Technology KNX
Brand ZENNIO
Mounting DIN Rail
Inputs 4
Input voltage KNX Bus (29VDC)
Outputs 6
IP rating IP20
Mounting Width 5MW

Documents & Downloads

Ivory Egg uses cookies to make your experience better and provide necessary site functionality. By using our website, you agree to set the cookies and accept the privacy policy