OCPP to Modbus TCP & RTU Server Gateway - 01 device
INTESIS INMBSOCP0010100

OCPP to Modbus TCP & RTU Server Gateway - 01 device

Product code: INMBSOCP0010100
Integrate Electric Vehicles Charging points based on OCPP 1.6 with any Modbus RTU or TCP controller. The aim of this integration is to make accessible basic operations of the Charging points from a Modbus PLC, making the BMS the Central System of the EV charging operation.
Price (Excluding GST)
$P.O.A

Description

FEATURES

  • Support for OCPP 1.6 JSON
  • Support for Modbus RTU and TCP
  • Flexible Modbus configuration (Baudrate, Data type)
  • OCPP Scan to search Chargers in the network
  • Fix Modbus register map
  • OCPP operations supported:
  • Authorize, RemoteStart/Stop Transaction, Start/StopTransaction, Local list management, HeartBeat and MeterValues
  • Reduced dimensions, compact housing
  • UL certified

This bidirectional gateway provides a straightforward and fast integration thanks to its unique onboard features.

Thanks to its support for the OCPP 1.6 standard and its basic operations, it guarantees a seamless integration with any standard Modbus PLC or controller.
The configuration is carried out using the Intesis MAPS software. Which allows you to define your own settings for the device. Also, it will be able to download all the available project templates or to import any created/exported project template on your computer.

Technical Details

Specification

Enclosure

  • Plastic, type PC (UL 94 V-0)
  • Net dimensions (dxwxh): 93x53x58 mm
  • Recommended space for installation (dxwxh): 100x60x70mm 
  • Colour: Light Grey. RAL 7035

Mounting

  • Wall.
  • DIN rail EN60715 TH35.

Terminal Wiring (for power supply and low-voltage signals)

  • Per terminal: solid wires or stranded wires (twisted or with ferrule)
  • 1 core: 0.5mm2... 2.5mm2 
  • 2 cores: 0.5mm2... 1.5mm2 
  • 3 cores: not permitted

Power

  • 1 x Plug-in screw terminal block (3 poles)
  • Positive, Negative, Earth 
  • 9-24VDC +/-10% Max.: 205mA

Ethernet

  • 1 x Ethernet 10/100 Mbps RJ45
  • 2 x Ethernet LED: port link and activity

Ethernet Port

  • 1 x Ethernet 10/100 Mbps RJ45
  • 2 x Ethernet LED: port link and activity
  • 1 x Serial EIA485 (Plug-in screw terminal block 3 poles) A, B, SGND (Reference ground or shield)
  • 1500VDC isolation from other ports

Switch A (SWA)

  • 1 x DIP-Switch for serial EIA485 configuration: 
  • Position 1: ON: 120  termination active. Off: 120  termination inactive (default)
  • Position 2-3: ON: Polarisation active (default) Off: Polarisation inactive

Operation Temperature

  • 0C to +60C

Operational Humidity

  • 5 to 95%, no condensation

Protection

  • IP20 (IEC60529)

Properties

Properties