KNX universal weather station
Description
Intended use
- Measurement and evaluation of weather data: wind speed, wind direction, precipitation, brightness, global radiation, twilight, temperature, relative air humidity and air pressure
- Installation on the outside of buildings, preferable in the roof and facade area
- Operation with additional power supply (ref.-no.: WSSV 10)
- Integrated GPS/GLONASS receiver for automated positioning
- Calculation of additional weather data: absolute air humidity, chill temperature, comfort
- Function for shading control
- Integrated KNX bus coupling unit
- Measuring and limit value monitoring
- Software logic modules for linking events
- Integrated heating
The weather station needs an operating voltage supply of 24 V AC, for example power supply module ref.-no. WSSV 10.
Spare part: fastening arm ref.-no.: 2225 BFA
Technical Details
Specification
Power supply
Rated voltage: AC 24 V SELV (± 10 %). DC 21 ... 32 V SELV
Current consumption: 100 ... 400 mA (dependent on the weather)
Protection class: III
Cable type: LiYCY 4xAWG26
Cable length: 5 m
Total length per line: 15 m
Number of weather stations: max. 3 (per line)
KNX medium: TP 256
Rated voltage KNX: DC 21 ... 32 V SELV
Current consumption KNX: max. 5 mA
Ambient temperature: −30 ... +60 °C
Stora/transport temperature: −25 ... +70 °C
Degree of protection: IP 44 (in position for use)
Dimensions (Ø x H): 130 x 68 mm
Wind direction sensor
Measuring range: 1 ... 360°
Resolution: 1°
Accuracy: ± 10 % (laminar wind stream)
Wind speed sensor
Measuring range: approx. 0 ... 40 m/s
Resolution: 0.1 m/s
Accuracy (≤ 10 m/s): ± 1 m/s
Accuracy (> 10 m/s): ± 5 %
Temperature sensor
Measuring range: −30 ... +60 °C
Resolution: 0.1 K
Accuracy: ± 1 K (wind > 2 m/s, for −5 ... +25 °C)
Precipitation sensor
Measuring range: yes / no
Accuracy: fine drizzle
Brightness sensors
Number: 4
Measuring range: approx. 0 ... 150 klx
Resolution: 1 klx
Accuracy: ± 3 %
Spectral range: 475 ... 650 nm
Dawn sensor
Measuring range: approx. 0 ... 900 lx
Resolution: 1 lx
Accuracy: ± 10 lx
Air pressure sensor
Measuring range: 300 ... 1100 hPa
Resolution: 0.01 hPa
Accuracy: ± 0.5 hPa (20 °C)
Humidity sensor
Measuring range: 0 ... 100 % relative humidity (r. h.)
Resolution: 0.1 % relative humidity (r. h.)
Accuracy: ± 10 % rel. humidity (20 °C)
Absolute humidity: 0 ... 400 g/m³
Resolution: 0.01 g/m³
Global radiation
Measuring range: 0 ... 1300 W/m²
Resolution: 1 W/m²
Accuracy: ± 10 %
Spectral range: 350 ... 1100 nm
Properties
Properties
Technology | KNX |
Brand | JUNG |