ZENNIO
ZCL-HP126
MAXinBOX Hospitality. Fan coil controller for 2/4-pipe unit with 2 16A C-load outputs and 6 a/d inputs
Product code:
ZCLHP126
MAXinBOX Hospitality is a fan-coil controller for 2 or 4 pipe units with up to three fan speeds and two 2-points valves. It has 2 outputs of 16A C-Load. Moreover, it has 6 analog-digital multifunction inputs that can be configured as binary inputs for sensors and potential-free push buttons, as temperature probe inputs or as motion sensor inputs. It includes Master Light function, 10 logical functions and allows the manual control of all the outputs with status indication through LEDs.
Description
- 7 outputs:
- 2 valve control outputs.
- 2 individual outputs- Suitable for capacitive loads, maximum 140 µF.
- 3 fan speed control outputs.
- Possibility to connect different phases in adjoining outputs.
- 6 analog/digital inputs.
- Manual output operation with push button and LED status indicator.
- Logical functions included.
- Output timing facilities.
- Total data saving on power failure.
- Size 67 x 90 x 80 mm (40.5 DIN units).
- KNX BCU integrated.
- DIN rail unit assembly (EN 50022), with snap fit clamp.
- CE directives compliant.
Technical Details
Specification
General System Specifications
- KNX Power Supply: 29VDC
- KNX Current Consumption: 10mA @ 29VDC
- Operating temperature: 0 ¡C to 55 ¡C
- Assembly: Independent control assembly device. Connect LUMENTO as near as possible to both, the load to dimmer and the external power supply.
- KNX bus failure response: Data saving and relays action according to parameterization.
- Response when restarting KNX bus: Data recovering and output status change according to parameterization.
- Operation Indicator: Programming LED indicates programming mode (red) and test mode (green). Output
status LED indicators reflect current output state.
Output Specifications
- Contact type: Potential free outputs through bistable relays with tungsten pre-contact.
- Disconnection type: Micro-disconnection
- Outputs per common -Individual/Valve outputs: 1 output per common
- Outputs per common -Fan outputs: 3 outputs per common
- Different phase connection (valve and individual outputs): Possibility to connect different phases in adjoining outputs
- Connection type: Terminal block (screw)
- Recommended cable section: 0.25 mm to 4 mm (26-10 AWG)
- Cable type: Stranded or solid wire
- Maximum response time: 50 ms
Individual Outputs:
- Rated current by output: 16A (6) 250V AC (4000 VA), 16A (6) 30V DC (480W)
- Maximum Power - Resistive load: 4000W
- Maximum Power - Inductive load: 1500VA
- Maximum inrush current: 800A/200_s or 165A/20ms
- Expected life - Mechanical: 3 million operations (60cpm)
- Expected life - Electrical: 100.000 cycles (6cpm/resistive load)
Fan & Valve Outputs:
- Rated current by output: 8A (4) 250V AC (2000 VA), 8A (4) 30V DC (240W)
- Maximum Power - Resistive load: 2000W
- Maximum Power - Inductive load: 1000VA
- Expected life - Mechanical: 1 million operations (180cpm)
- Expected life - Electrical: 50.000 cycles (6cpm/resistive load)
Input Specifications
- Number of inputs per common 6
- Input voltage: +3.3V DC for the common
- Input current: 1.0mA @ 3.3V DC (each input)
- Input impedance: Approx. 3.3k ½
- Switching type: Dry voltage contacts between input and common
- Connection method: Cable screw terminal
- Max. cable length: 30 m.
- NTC probe length: 10.5 m. (up to 30m.)
- NTC accuracy (@ 25 ¡C): 0.5 ¡C
- Temperature measure precision: 0.1 ¡C
- Cable cross-section: 0.15 mm to 20.5 mm (26-12 AWG)
- Response time: Max 10ms.
Properties
Properties
Technology | KNX |
Brand | ZENNIO |
Mounting | DIN Rail |
Inputs | 6 |
Input voltage | KNX Bus (29VDC) |
Outputs | 7 |
IP rating | IP20 |
Mounting Width | 5MW |