MAXinBOX 12. KNX Multifunction actuator with KNX Secure - 12 outputs 16 A
ZENNIO ZIO-MB12

MAXinBOX 12. KNX Multifunction actuator with KNX Secure - 12 outputs 16 A

Product code: ZIOMB12
MAXinBOX 16 V3 is a multifunction actuator for DIN rails that offers multiple configurations of up to 8 shutter channels, up to 16 independent outputs of 16A (capacitive loads supported) and up to 4 blocks of 2-pipes fan coil controller. It allows manual control of its outputs thanks to the push buttons on the cover. It includes 20 independent logical functions.
Price (Excluding GST)
$P.O.A

Description

  • 4 different configurable blocks:
    • Shutter channels (up to 8).
    • Individual outputs (up to 16).
    • 2-pipe fan coil control (up to 4 units).

  • Manual output operation with push button and LED status indicator.
  • Suitable for capacitive loads, maximum 140 µF.
  • Logical functions included.
  • Output timing facilities.
  • Total data saving on power failure.
  • Size 90 x 60 x 140 mm (8 DIN units).
  • DIN rail unit assembly (EN 50022), with snap fit clamp.
  • No external power supply required other than the bus.
  • KNX BCU integrated.
  • Possibility to connect different phases in adjoining outputs.
  • CE directives compliant



Technical Details

Specification

General System Specifications

  • KNX Power Supply: 29VDC
  • KNX Current Consumption: 11mA @ 29VDC
  • Operating temperature: 0 ¡C to 55 ¡C
  • Assembly: Independent control assembly device to be mounted inside of electrical panels with DIN rail (EN 50022).
  • Response to Bus Voltage Failure: Data saving and relay status change according to parameterization.
  • Response to bus failure recovery: Data recovering and output status change according to parameterization 
  • Operation indication:  Programming LED indicates programming mode (red) and test mode (green). Output status LED indicators reflect current output state.

Outputs:

  • Contact type: Potential free outputs through bistable relays with tungsten pre-contact.
  • Disconnection type: Micro-disconnection
  • Rated current by output: 16(6)A * 250V AC (4000 VA) 16(6)A * 30V DC (480W)
  • Number of outputs per common: 1 shutter channel
  • Different phases connection:  Possibility to connect different phases in adjoining shutter channel outputs 
  • Max Current per Block: 40A
  • Max Power - Resistive Load:  4000W
  • Max Power - Inductive Load: 1500VA
  • Connection type: Cable screw terminal
  • Recommended Cable Section: 0.25 mm to 4 mm 
  • Cable Type: Stranded or Solid Wire
  • Maximum Response Time:  50ms
  • Expected Life - Mechanical: 3 million operations (60cpm)
  • Expected Life - Electrical: 100.000 cycles (6cpm with resistive load)

Properties

Properties

Technology KNX
Brand ZENNIO
Mounting DIN Rail
Input voltage KNX Bus (29VDC)
Outputs 12
IP rating IP20
Mounting Width 6MW
KNX Secure Yes

Documents & Downloads