ZENNIO
ZIO-IB24V3
inBOX 24 . KNX multifunction actuator for flush mounting - 2 outputs 16A/4 inputs A/D
Product code:
ZIO-IB24V3
Multifunction actuator for flush mounting with 2 outputs (16A C-Load) which offer multiple configurations as shutter channel or individual outputs. It allows manual control of its outputs and includes 4 thermostats, 10 independent logical functions and Master-Light function. In addition, it incorporates 4 analog-digital inputs that may be configured as binary inputs for sensors and potential-free push buttons, as temperature probe inputs or as motion sensor inputs.
Description
- 2 outputs configurable as:
- Shutter channel
- Individual outputs (up to 2)
- 4 inputs configurable as:
- Binary input
- Temperature probe (with application 1.2 support third party NTC Probes)
- Motion sensor
- 10 logical functions
- 4 Thermostats
- Total data saving on KNX bus failure
- Integrated KNX BCU
- Dimensions Ø 50 x 26mm
- Can be mounted within distribution boxes, junction boxes or wall back boxes
- Conformity with the CE directives
Technical Details
Specification
General System Specifications
- KNX Power Supply: 29VDC
- KNX Current Consumption: 5.22mA @ 29VDC
- Operating temperature: 0 °C to 55 °C
- Assembly: Can be mounted within distribution boxes, junction boxes or wall back boxes
- Response to Bus Voltage Failure: Data saving and relays action according to parameterization.
- Response to bus failure recovery: Data recovering and output status change according to parameterization.
- Operation indication: Programming LED indicates programming mode (red) and test mode (green). Output status LED indicators reflect current output state.
Outputs
- Number of outputs: 2 outputs
- Contact type: Potential free outputs through bistable relays with tungsten pre-contact.
- Disconnection type: Micro-disconnection
- Rated current by output: 16(6)A * 250V AC (4000 VA), 16(6)A * 30V DC (480W)
- Maximum inrush current: 800A/200 microsecond (fluorescent lamps), 165A/20 millisecond (resistive lamps)
- Outputs per common (Channel): 1 individual output
- Total max current in device: 20A
- Max Power - Resistive Load: 4000W
- Max Power - Inductive Load: 1500VA
- Connection type: Cable screw terminal
- Recommended Cable Section: 0.5 mm2 to 4 mm2
- Cable Type: Stranded or Solid Wire
- Maximum Response Time: 50ms
- Expected Life - Mechanical: 3 million operations (60cpm)
- Expected Life - Electrical: 100.000 cycles (6cpm with resistive load)
Inputs
- Number of inputs per common: 4
- Input voltage: +3.3V DC for the common
- Input current: 1.0mA @ 3.3V DC (each input)
- Input impedance: Approx. 3.3kohm
- Switching type: Dry voltage contacts between input and common
- Connection method: Cable screw terminal
- Max. cable length: 30 m.
- NTC probe length: 10.5 m (up to 30m)
- NTC accuracy (@ 25 °C): 0.5 °C
- Temperature measure precision: 0.1 °C
- Cable cross-section: 0.5 mm2 to 1 mm2 (24-16 AWG)
- Response time: Max 10ms
Properties
Properties
Technology | KNX |
Brand | ZENNIO |